Automatic Transfer Switches Controllers

ATS-01

Programmable Automatic Transfer Switch (ATS) Controller

ATS-01 is the programmable micro-processor based design automatic transfer Switch (ATS) Controller. There is no need for PC connection or software driver, all operation and program can be accessed directly on ATS-01 front panel. Optional accessories of TSP-01 or TSP-02 transformer module and exclusive ATS harness can simplify the set up and connection time.

BrochureManual3D DisplayController Assembly

Features

  • Micro-Processor Based Design
  • Compact Size with User-Friendly LED Display
  • Simple Push Button Programming & Operation (here is no need for PC connection or software--all operation can be done directly on ATS-01 front panel)
  • Provides 3 or 1 Phase Volt. / Freq. Monitoring & Protection For Both Normal & Emergency Sources
  • Transfer Fail Alarm, Pre-exerciser or Pre-transfer Signal Output
  • Remote Engine Start Signal
  • Built-in Weekly Exerciser Timer
  • No Generator Battery Connection Needed (Program settings are auto-saved into memory and will remain saved even when power is disconnected)

Specifications : ATS-01

Input Control Voltage 160~250 VAC
50/60 Hz
Voltage Measurement Range 80~550 VAC
50/60 Hz
Frequency Measurement Range 45~70 Hz
Generator Start Relay 7A @ 250 VAC Max.
Transfer to Normal Relay 7A @ 250 VAC Max.
Transfer to Standby Relay 7A @ 250 VAC Max.
Alarm output Auxiliary Relay 0.5A @ 120 VAC
1.0A @ 24 VDC
Environment Operating Temperature : -20~70 °C
Storage Temperature : -35~85 °C
Operating Humidity : Maximum 95%
All Phase Voltage & Frequency Monitoring Over Voltage Adjustable Range : 110~550 VAC
Under Voltage Adjustable Range : 80~470 VAC
Over Frequency Adjustable Range : 51~70 Hz
Under Frequency Adjustable Range : 45~59 Hz
Adjustable Timers TDNE : 0~300 sec.
TDES : 0~30 sec.
TDEN : 0~300 sec.
TDEC : 0~300 sec.
Pre-transfer Signal : 1~99 sec.
Pre-exerciser Signal : 1~99 sec.
Engine Exerciser Test Period : 1~60 min.
4 Digit 7 Segment LED Display
  • Programmable display with 3 phase voltage & frequency
  • Internal program settings & status display
  • TDEN, TDNE & TDEC real time countdown display
User-Friendly Status LED Display
  • Display AUTO/TEST Status
  • Over / Under Volts & Freq. (Both Normal & Emergency)
  • Display Real Time Power Loop
Panel Installation Cut-Out 113.0 x 168.0 ± 0.5 mm