ATS-PLC Touch Screen Automatic Transfer Switches Controllers

ATS-PLC

Touch Screen Programmable Automatic Transfer Switch (ATS) Controller

The ATS-PLC a Programmable Automatic Transfer Switch (ATS) Controller with 5.7" Colorful Touch Screen. It is equipped with all of the necessary functions and provides excellent monitoring and protection for normal and emergency load. It is equipped with optional USB, RS485, and Ethernet remote communication functions to allow remote operation.

Features

Optional KCU modules for USB / RS485 / Ethernet remote control
Optional KCU modules for USB / RS485 / Ethernet remote control
  • Micro-processor based design
  • Compact size with 5.7" colorful screen
  • Simple touch panel for programming & operation *1
  • Provides Volt / Freq. monitoring & protection for both normal & emergency sources
  • Provides reverse phase sequence monitoring & protection
  • Provides over current or short circuit monitoring & protection
  • Optional KCU modules for USB / RS485 / Ethernet remote control
  • Built-in 1 to 4 weeks exerciser timer
  • Multi-language support
  • Build-in 4 digitals password & 40 event logs functions

Specifications

  • Power Supply Voltage
  • 8 to 60 Vdc
  • CT Specification
  • Burden Above 2.5 VA
  • CT Secondary Rated Amps
  • 5A
  • Generator Start Relay
  • 7A @ 250 Vac Max.
  • Transfer to Normal Relay
  • 7A @ 250 Vac Max.
  • Transfer to Standby Relay
  • 7A @ 250 Vac Max.
  • Alarm Output Auxiliary Relay
  • 7A @ 250 Vac Max.

Colorful Touch Screen Specifications

  • Display Type
  • a-Si TFT
  • Display Size
  • 5.7" Diagonal
  • Resolution
  • 640 x RGB x 480
  • Color Depth
  • 262K
  • Pixel Size
  • 0.18 x 0.18 mm
  • Active Area
  • 115.2 x 86.4 mm (W x H)
  • Backlight Type
  • LED

Full Phase Voltage & Frequency Monitoring

  • Over Voltage Adjustable Range
  • 110 to 530 Vac
  • Under Voltage Adjustable Range
  • 80 to 470 Vac
  • Over Frequency Adjustable Range
  • 51 to 75 Hz
  • Under Frequency Adjustable Range
  • 40 to 59 Hz

Adjustable Timers

  • TDNE
  • 0 to 1800 seconds
  • TDES
  • 0 to 300 seconds
  • TDEN
  • 0 to 1800 seconds
  • TDEC
  • 0 to 1800 seconds
  • TDOFF
  • 0 to 300 seconds
  • Engine Exerciser Test Period
  • 0 to 120 minutes
  • Exerciser Test Cycle
  • 1 to 4 weeks

Environment

  • Operating Temperature
  • -20 to +70 °C
  • Storage Temperature
  • -30 to +80 °C
  • Relative Humidity
  • Max. 90%

Physical Specifications

  • Panel Cut-Out
  • 137.0 x 137.0 +/-0.2 mm
  • Dimensions
  • 148.0 (L) x 148.0 (W) x 61.5 (H) mm
  • Weight
  • 750 g +/-2%