Battery-powered Automatic Flashing Unit for Generator

EB-9V

Battery-powered Automatic Flashing Module

EB-9V automatic flashing module is installed with a built in 9V lithium battery which helps the generator to establish voltage build up at initial stage; No external battery and DC power supply are required. the excitation power is supplied by the internal battery.

Features

  • No external battery or DC power supply required, excitation power provided by an internal battery
  • Small size, light weight and easy installation saving labor
  • Automatic excitation detection requires no manual operation or setting
  • Very low static power consumption, Up to 3 years between battery replacement in standby mode
  • Battery low voltage indicator reminds user to change battery
  • Up to three repeat flashing attempts and will automatically stop when voltage builds up
  • Excitation failure indicator. Resets automatically when voltage builds up or engine is stopped
  • Battery Reverse Polarity Protection
  • Excitation field F+, F- Reverse Polarity Protection
  • Built in manual forced excitation push button

Electrical Specifications

  • Sensing Voltage Input
  • Voltage 1 to 300 Vac 1 phase 2 wire
    Frequency 50/60 Hz
  • Excitation Output
  • Voltage 9 Vdc
    Current 700 mA Max.
  • Flashing Output Conditions
  • When voltage less than 10Vac at frequency greater than 40Hz
  • Flashing Output Time
  • Excitation output 5 seconds. Up to 3 attempts at 5 second intervals
  • Operating Temperature
  • -20 to +60 °C
  • Storage Temperature
  • -40 to +60 °C
  • Relative Humidity
  • Max. 95%
  • Vibration
  • 5 Gs @ 60 Hz
  • Dimensions
  • 87.0 (L) x 41.5 (W) x 61.7 (H) mm
    3.42 (L) x 1.63 (W) x 2.43 (H) inch
  • Weight
  • 85 g +/-2%
    0.19 lb +/-2%

Lithium Battery Specifications

  • Model No.
  • ULTRALIFE U9VL-J-P
  • Voltage
  • 9 Vdc
  • Current
  • Normal Discharge 700 mA Max.
    Pulse Discharge 1050 mA Max.
  • Capacity
  • 1200 mAh @ 23°C
  • Service Life
  • 10 years

Downloads

Dimensions


Recommended Connections