EC-01 Auto Start Module for Gasoline Engine Generators

EC-01

Auto Start Module for Gasoline Engine Generators

EC-01 adds remote start/stop capability to gasoline generators equipped with electric start motors. EC-01 Auto Start Module enables a gasoline generator to be started and stopped remotely with signals from any Automatic Transfer Switch (ATS) controller.

220 Vac Input Voltage only model available (EC-01-220V).

Features

  • Adds remote start/stop capability to gasoline generators with electric start motors
  • Small size and low power consumption
  • Connects by a terminal block for easy installation and replacement
  • Built in fuse for the direct current (DC) protection
  • Three Engine Cranking Attempts
  • LED status indicators
  • Adjustable time delay setting potentiometers
  • Auxiliary Dry Contact Output

Specifications

  • DC Power Input
  • 12 / 24 Vdc
  • AC Power Input
  • Voltage 110 / 220 Vac 1 phase
    Frequency 50 to 60 Hz
  • Start-up Signal Output
  • 6A (Battery Positive Output)
  • Start-up Signal Output
  • 4A (Battery Negative Output)
  • Auxiliary Dry contact Output
  • 4A
  • Static Power Dissipation
  • Max. 3 watts
  • Operating Temperature
  • -25 to +80 °C
  • Relative Humidity
  • Max. 95%

Timer Settings and Adjustment

  • Engine Start Cranking Time
  • 1 to 20 seconds
  • Engine Cranking Time Interval
  • 1 to 10 seconds
  • Engine Shutdown Time Delay
  • 1 to 20 seconds

LED Indicators

  • Remote Start
  • Engine Running
  • Engine Fail to Start

Downloads

Dimensions

Rotating Image

Accessories