Contact Us | Site Map | News | About Us | Test Report | Home

EA321

Automatic Voltage Regulator for PMG Generator

Home > Generator Automatic Voltage Regulator > Newage Series AVR > EA321

Newage MX321 PMG Automatic Voltage Regulators Replacements

EA321 3 Phase Sensing Permanent Magnet Generator type voltage regulator is a compatible replacement for Newage Stamford MX321 regulator.

» Brochure | Manual | 3D Display

Features

Specifications

Sensing Input Voltage 190~264 VAC, 2 or 3 Phase
Frequency 50/60 Hz Selectable
Power Input(PMG) Voltage 170~220 VAC, 3 Phase 3 Wire
Current 3A/Phase
Frequency 100~120Hz Nominal
Output Voltage Max. 120 VDC
Current Continuous 3.7A, Intermittent 6A for 10 sec.
Resistance Min. 15 Ω
Voltage Regulation < ±0.5% RMS (with 4% engine governing)
Voltage Build-up Residual volts at AVR terminal > 5 VAC
Soft Start Ramp Time 0.4~4 sec. adjustment
Thermal Drift 0.05% per °C change in AVR ambient
Current Limit Input Burden: 10 Ω, Sensitivity range: 0.5~1A
Unit Power Dissipation Max. 18 Watt
External Volts Adjustment ±10% with 1 KΩ 1 watt trimmer
Over Excitation Protection Set point 75 VDC, Time delay 8~15 sec.
Under Frequency Protection(UFRO) Set point : 95% Hz (Factory set)
Slope : 100~300% down to 30 Hz
Max. Dwell : 20% volts/sec. recovery
Analogue Input(Adjustable Parameters) Max. Input ± 5 VDC
Sensitivity 1V for 5% generator volts
Input Resistance 1 KΩ
Droop Input Burden : 10 Ω
Max. sensitivity : 0.22A for 5% droop (PF=0)
Max. input : 0.33A
Over Voltage Detector Input Set point : 300V, Time delay 1sec.(fixed)
CB Trip Coil Volts : 10~30 VDC / 0.5Amp
Environment
  • Vibration : 3.3 G @ 100~2 KHz
  • Relative Humidity : Maximum 95%
  • Operating Temperature : -40~70 °C
  • Storage Temperature : -40~85 °C
AVR Controls Functions
  • VOLT : Output Voltage Adjustment
  • STAB : Stability Adjustment
  • UFRO : UFRO Knee Point Set
  • DROOP : To Set the Droop to 5% at PF=0
  • TRIM : To Optimize Analogue Input Sensitivity
  • EXC : Over Excitation Trip Level Set
  • DIP : Hz Related Voltage DIP Set
  • DWELL : Hz Related Recovery Time Set
  • I LIMIT : Stator Current Limit Set
  • OVER V : Over Voltage Trip Level Set
  • RAMP : No Load Voltage Ramp Set Time
  • RMS : Root Mean Square of Generator
Dimensions 203.0(L) x 153.0(W) x 39.1(H) mm
Weight 530 g ± 2%

Mechanical Specifications

Mechanical Specifications

Related Products

MX341 Replacements Voltage Regulator Permanent Magnet Generators
EA341
Generators AVR Newage SX440 Replacements
EA440
Generators Voltage Regulators Compatible with Newage SX460
EA460
Newage Stamford SX440 AVR Replacements
EA440-T

▲Return to top

Use for reference purpose only and not a genuine Newage product.