Newage MX321 PMG Automatic Voltage Regulators Replacements

EA321

Automatic Voltage Regulator for PMG Generator

EA321 3 Phase Sensing Permanent Magnet Generator type voltage regulator is a compatible replacement for Newage Stamford MX321 and Onan 305-0823.

BrochureManual3D Display

Features

  • < ± 0.5% RMS Regulation
  • For Use In Parallel Operation
  • RAMP, DIP, DWELL, DROOP, RMS, U/F, Over Voltage & Over Excitation Adjustment Functions
  • Over Exc. / Over Volt. & UFRO LED Indicators
  • Current Limiting Function

Specifications : EA321

Sensing Input Voltage 190~264 VAC, 2 or 3 Phase
Frequency 50/60 Hz Selectable
Power Input(PMG) Voltage 170~220 VAC, 3 Phase 3 Wire
Current 3A/Phase
Frequency 100~120 Hz Nominal
Output Voltage Max. 120 VDC
Current Continuous 3.7A, Intermittent 6A for 10 sec.
Resistance Min. 15Ω
Voltage Regulation < ± 0.5% RMS (with 4% engine governing)
Voltage Build-up Residual volts at AVR terminal > 5 VAC
Soft Start Ramp Time 0.4~4 sec. adjustment
Thermal Drift 0.05% per °C change in AVR ambient
Current Limit Input Burden 10Ω
Sensitivity Range 0.5~1A
Unit Power Dissipation Max. 18 Watt
External Volts Adjustment ± 10% with 1 KΩ 1 watt trimmer
Over Excitation Protection Set point 75 VDC, Time delay 8~15 sec.
Under Frequency Protection(UFRO) Set point : 95% Hz (Factory set)
Slope : 100~300% down to 30 Hz
Max. Dwell : 20% volts/sec. recovery
Analogue Input(Adjustable Parameters) Max. Input ± 5 VDC
Sensitivity 1V for 5% generator volts
Input Resistance 1 KΩ
Droop Input Burden 10Ω
Max. Sensitivity 0.22A for 5% droop (PF=0)
Max. Input 0.33A
Over Voltage Detector Input Set Point 300V, Time delay 1sec.(fixed)
CB Trip Coil Volts 10~30 VDC / 0.5 Amp
Environment Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C
Relative Humidity : Maximum 95%
Vibration : 3.3G @ 100~2 KHz
AVR Controls Functions VOLT : Output Voltage Adjustment
STAB : Stability Adjustment
UFRO : UFRO Knee Point Set
DROOP : To Set the Droop to 5% at PF=0
TRIM : To Optimize Analogue Input Sensitivity
EXC : Over Excitation Trip Level Set
DIP : Hz Related Voltage DIP Set
DWELL : Hz Related Recovery Time Set
I LIMIT : Stator Current Limit Set
OVER V : Over Voltage Trip Level Set
RAMP : No Load Voltage Ramp Set Time
RMS : Root Mean Square of Generator
Dimensions 203.0(L) x 153.0(W) x 39.1(H) mm
Weight 530 g ± 2%

Mechanical Specifications

Mechanical Specifications