Automatic Mains Failure Control & Protection Modules

AMF-10

Automatic Mains Failure Control & Protection Module

The AMF-10 is an universal Automatic Mains Failure Control & Protection Module. It is a control and protection module for the generator and a monitoring controller for the Automatic Transfer Switch. The modularity design with easy to read high illuminant LED display, universal warning symbols and easy to operate interface, all functions settings can be programmed directly from the front panel. Optional AMF-10R universal AMF Controller Interface Module (relay module) is available for the AMF-10 to simplify the wiring and connection process.

BrochureManual3D Display

Features

  • Micro-Processor Auto Control & Protection
  • Easy to Read High Light LED Display
  • Modularity Design, Easy to Install
  • Compact Size with Vibration Protected
  • Waterproof Front Panel With IP65
  • Provide Full Mains and Genset Alarms Signals shutdowns
  • All Functions Setting Can be Done Directly On AMF-10 No Need For PC Connection (Customized settings are auto-saved into memory and will remain even when power is off)
  • Universal LED Graphic Interface, Displays ATS and Genset Status and Failures

Specifications : AMF-10

Power Input Voltage 9~36 VDC (12V , 24V)
Sensing Input Voltage 15~510 VAC
Frequency 50/60 Hz
Rated Output Capacity DC 10 Amps @ 12/24 VDC
AC 8 Amps @ 250 VAC
CT Secondary RatedAmps 5A
CT Specifications Burden 2.5 VA
Power Dissipating Max. 7 Watt
Max. Vibration 5~25 Hz , ± 1.6 mm , 25~100 Hz , a=4g
4 Digit 7 Segment Easy-to-Read LED Display
  • Programmable Display with 3 Phase Volts,Amp & Freq.
  • Engine Operation Hours & Battery Voltage Display
  • Internal Program Settings & Status
  • Failure Signal Status By Graphic Display
Protection & Alarm Status
  • Engine Start Failure
  • High Coolant Temperature.
  • Engine Over Speed
  • Abnormal AC Voltage
  • Low Fuel Level
  • Maintain Service Alarm
  • Emergency Stop
  • Low Oil Pressure
  • Engine Under Speed
  • Generator Over Load
  • Abnormal Battery Voltage
  • Programmable Alarm
Environment Operation Temperature : -20~70 °C
Relative Humidity : Maximum 95%
Panel Installation Cut-Out 137.0 x 137.0 ± 0.5 mm
Weight 610 g ± 2%

Mechanical Specifications

Mechanical Specifications

▲Return to top