BTB Type ATS Programmable Automatic Transfer Switch

BTB Type ATS

Programmable Automatic Transfer Switch
2P/3P/4P 100Amp & 250Amp & 2P 400Amp

BTB type Automatic Transfer Switch integrates the programmable controller and transfer switch, saving users a lot more time on setting and installation.

It can be operated both electrically and manually; through the colored LCD display panel, all information is clear at a glance. BTB series is available for 2P/3P/4P 100Amp & 250Amp & 2P 400Amp system, and the system voltage is between 110V to 480V. Made with Moulded Case Circuit Breaker (MCCB) provides Over current protection. The equipped mechanical and electrical interlock protections & safety lock both efficiently prevent the personnel and gensets from potential injury or damage. With optional communication modules, users are enabled to control and monitor the gensets remotely.

  • TAIWAN Pat. No. M553490

Features

  • Integrated programmable controller with switch save space, installation time and cost
  • MCCB type with available as Class CB / Class PC models
  • Electrical and Manual operation, Lug connections to avoid crimping
  • Safety lock to avoid injury to personnel during maintenance
  • Color LCD display allows direct input of settings
  • All phase voltage/frequency monitor & protection for Utility & Generator
  • Auxiliary contacts to indicate Utility or Generator MCCB closed
  • Adjustable central “OFF” position timer
  • Adjustable Weekly exercise timer from 1 to 4 weeks
  • Both mechanical and electrical interlock protections
  • Complies with IEC60947-6-1 and AC-33A Utilization Category
  • Optional communication modules for remote monitoring and control with a Smartphone
  • Option of English, Spanish or Traditional Chinese language display
  • All fault message accompany by an audio alarm to notify the user

Indoor and outdoor enclosure available for selection

Indoor and outdoor enclosure available for selection

MCCB Rated Current and Rated Breaking Capacity (Class CB only)

No. of Poles Rated Insulation
Voltage Ui (V)
Rated Current (A)
Ambient Temperature
40°C
Rated Breaking Capacity
IEC 60947-2 Icu / Ics (KA)
220V / 240V 380V / 415V 440V 550V
2P / 3P / 4P 690 100 / 250 50 / 25 30 / 15 25 / 13 20 / 10
2P 690 400 50 / 25 30 / 15 25 / 13 20 / 10

Specifications

  • Operating Voltage
  • Refer to
  • Rated Frequency
  • 50/60 Hz
  • Remote Start Output
  • 7A @ 250 Vac Max.
  • Auxiliary Output
  • 3A @ 250 Vac Max.

Adjustable Timer Settings

  • TDNE Time Delay Normal to Emergency
  • 0 to 250 seconds
  • TDES Time Delay Engine Start
  • 0 to 15 seconds
  • TDEN Time Delay Emergency to Normal
  • 0 to 999 seconds
  • TDEC Time Delay Engine Cool-down
  • 0 to 250 seconds
  • TDOF Time Delay in OFF position
  • 0 to 99 seconds

Environment

  • Operating Temperature
  • -20 to +60 °C
  • Storage Temperature
  • -30 to +80 °C
  • Relative Humidity
  • Less than 90%

Physical Specifications

  • Dimensions
  • 2P: 225.0 (L) x 293.0 (W) x 170.0 (H) mm
    3P: 225.0 (L) x 293.0 (W) x 170.0 (H) mm
    4P: 225.0 (L) x 293.0 (W) x 205.0 (H) mm

Downloads


GenOnCall® - Remote App for mobile devices

Dimensions


Optional Accessories

ModBus Communication Module
SNMP Communication Module (Coming soon)
Ethernet Remote Communication Module for Dynamic IP Connection
Wi-Fi Remote Communication Module

Interface for Remote Communication Module

-

Click each specifications in the table below to obtain correct Model No.

No. of poles IEC Category Rated Current Safety Certification Applicable Voltages (VAC) Enclosure
2 2P (1P/2W) B Class CB *1 1 100A U UL Certified *4 1 100/ 110/ 120 Blank No enclosure
3 3P (3P/3W) P Class PC *2 2 250A X Standard 2 200/ 220/ 240 C With indoor enclosure
4 4P (3P/4W) 3 400A *3 3 380 / 415 E With outdoor enclosure
4 440/ 460/ 480
D 110 to 480 *5