ADVR-2100M AVR compatible with Marathon DVR2000 Series

ADVR-2100M

Automatic Voltage Regulator (AVR) substitutes for Marathon DVR2000 Series

ADVR-2100M is a hybrid Analog/Digital AVR that replaces Marathon DVR2000 Series. It can be either single or three phase sensing and PMG. It has Over Excitation Protection and also the capabilities for DROOP Parrelleling.

* It cannot be used with KUTAI IVT Generator Excitation Booster. If the AVR is intended to be used with IVT-1260 or IVT-2460, ADVR-2200M is the recommended model.

Features

  • Power input single phase 60 to 300 Vac @ 50 to 500 Hz
  • Sensing input 1 or 3 phase 220 to 600 Vac programmable
  • Voltage regulation less than +/-0.5%
  • 50/60 Hz selectable
  • Multiple power input source SHUNT, AUX, HARMONIC, PMG
  • Inverse-time over excitation and under frequency protection
  • Soft start voltage ramping
  • Built-in high capacity protection fuse
  • Panel mounted, internal wiring external adjustment

Specifications

  • Sensing Input
  • Voltage 220 to 600 Vac 1 phase or 3 phase DIP switch setting
    Frequency 50/60 Hz DIP switch setting
  • Power Input
  • Voltage 60 to 300 Vac 1 phase 2 wire
    Frequency 50 to 500 Hz
  • Excitation Output
  • Voltage Continuous 125 Vdc @ power input 220 Vac
    Current Continuous 5A Intermittent 7A for 10 seconds
    Resistance ≧ 13 ohms @ power input 110 Vac / ≧ 25 ohms @ power input 220 Vac
  • External Voltage Adjustment
  • Max. +/-5% @ 500 ohms 1 watt potentiometer
    Max. +/-10% @ 1K ohms 1 watt potentiometer
  • Voltage Regulation
  • Less than +/-0.5% (with 4% engine governing)
  • Build Up Voltage
  • 5Vac 25Hz residual volts at power input terminal
  • Soft Start Ramp Time
  • 4 seconds +/-10%
  • EMI Suppression
  • Internal electromagnetic interference filtering
  • Static Power Dissipation
  • Max. 12 watts
  • Burden in Shunt & PMG Wiring
  • 550 VA @ power input 110 Vac
    1100 VA @ power input 220 Vac
  • Quadrature Droop Input
  • CT 1A or 5A greater than 5VA (DIP switch setting)
    Sensitivity Max. +/-7% @ P.F +/-0.7
  • Analogue Input
  • Input resistance greater than 2K ohms
    Max. Input +/-5 Vdc or +10 Vdc
    Sensitivity 1 Vdc for 2.5% Generator Volts
  • Under Frequency Protection (Factory Presets)
  • 50 Hz system knee point at 45 Hz
    60 Hz system knee point at 55 Hz
  • Over Excitation Protection
  • Inverse-time 125 +/-4 Vdc @ power input 220 Vac
  • Voltage Thermal Drift
  • Less than 3% at -40 to +70 °C

AVR Control Functions

  • VOLT
  • Voltage adjustment
  • STAB
  • Stability adjustment
  • U/F
  • Setting under frequency protection knee point
  • DROOP
  • Droop adjustment
  • TRIM
  • Analogue input adjustment
  • DIP
  • Voltage droop ratio setting

Indication LED

  • O/E
  • Over excitation protection indicator
  • U/F
  • Under frequency protection indicator

Environment

  • Operating Temperature
  • -40 to +60 °C
  • Storage Temperature
  • -40 to +85 °C
  • Relative Humidity
  • Max. 95%
  • Vibration
  • 5.5 Gs @ 60 Hz

Physical Specifications

  • Dimension
  • 150.0 (L) x 135.0 (W) x 55.5 (H) mm
    5.91 (L) x 5.31 (W) x 2.19 (H) inch
  • Weight
  • 470 g +/-2%
    1.04 lb +/-2%